CP Chamber Parts

Machine wiring

Wire numbers by machine

Select a machine or search across the complete wire register.

Import Excel
Clear

Wire register

46 results
MachineWire numberName / definitionOptional extraNotesFromTo
Salt Spray Standard120 - 13001Cabinet mains live distribution feed to heater circuitsNOListed on page 1 as a cabinet-mains (>3 A) wire identifier.Edit
Salt Spray Standard120 - 130010Over-temperature stat input (O/T chain)NOO/T 1 and O/T 2 are wired in series on page 4.Edit
Salt Spray Standard120 - 13001004Air saturator heater mains feed between MCB8 and relay K1NOEdit
Salt Spray Standard120 - 130011Series link between O/T 1 and O/T 2 thermostatsNOEdit
Salt Spray Standard120 - 1300123ACC20 full switch inputYESACC20 — Waste Water Trough & Pump SystemEdit
Salt Spray Standard120 - 130014Moist air solenoid Y4NOEdit
Salt Spray Standard120 - 1300144Internal illumination relay switched-contact busYESInternal Illumination (OPTION)Edit
Salt Spray Standard120 - 1300147Salt tank low water alarm inputYES — MODEL/OPTIONSalt Tank Low Water Alarm option; standard on E/F/GDrawing notes this option is fitted as standard to models E, F and G.Edit
Salt Spray Standard120 - 130015Cabinet mains live conductor in the Q1 / RC1 power-management pathNOListed on page 1 as a cabinet-mains (>3 A) wire identifier.Edit
Salt Spray Standard120 - 130016Cabinet mains live conductor from RC1 toward ELEC516.1NOShown in the non-integral mains-filter arrangement.Edit
Salt Spray Standard120 - 130018Emergency stop inputNOEdit
Salt Spray Standard120 - 130019Canopy open switch inputNOPage 4 shows the associated pneumatic sensor switch circuit.Edit
Salt Spray Standard120 - 1300190Cabinet mains (>3 A) identifier listed in the wire standardNONot otherwise observed on pages 2-8 of this issue.Edit
Salt Spray Standard120 - 13002Cabinet mains neutral / common returnYES — SHAREDChart Recorder / accessory circuits — shared mains returnAlso feeds optional chart-recorder/accessory circuits.Edit
Salt Spray Standard120 - 130020Air saturator auto-fill solenoid Y1NOEdit
Salt Spray Standard120 - 1300200Cabinet mains (>3 A) identifier listed in the wire standardNONot otherwise observed on pages 2-8 of this issue.Edit
Salt Spray Standard120 - 130021Air saturator FULL optical sensorNOEdit
Salt Spray Standard120 - 130022Air saturator LOW optical sensorNOEdit
Salt Spray Standard120 - 130023Vent solenoid Y2NOEdit
Salt Spray Standard120 - 1300236Emergency-stop / canopy solenoid interlock conductorNOOne of the paired interlock conductors shown between S4 and the canopy-solenoid circuit.Edit
Salt Spray Standard120 - 1300237Emergency-stop / canopy solenoid interlock conductorNOOne of the paired interlock conductors shown between S4 and the canopy-solenoid circuit.Edit
Salt Spray Standard120 - 130024+24 V DC control railYES — SHAREDMultiple optional accessories — shared DC control railEdit
Salt Spray Standard120 - 130025Open canopy command / solenoid Y10NOCanopy interlock wiring also passes through the emergency-stop circuit.Edit
Salt Spray Standard120 - 130026Dry air solenoid Y3NOEdit
Salt Spray Standard120 - 130027Close canopy command / solenoid Y11NOCanopy interlock wiring also passes through the emergency-stop circuit.Edit
Salt Spray Standard120 - 130028Canopy closed proximity switch inputNOEdit
Salt Spray Standard120 - 130031Pump motor black lead (M1 / M6 via PERC010)YES — SHAREDPump Motor 2 / second pump shares this motor-lead identifierUsed on the standard pump and the optional/model-specific second pump.Edit
Salt Spray Standard120 - 130034BuzzerNOEdit
Salt Spray Standard120 - 130035Air saturator heater E2 load conductorNOListed on page 1 as a cabinet-mains (>3 A) wire identifier.Edit
Salt Spray Standard120 - 130036Air saturator heater controlNOEdit
Salt Spray Standard120 - 130037Chamber / cabinet heater relay K2 controlNOPLC page names the output 'Chamber Heater'.Edit
Salt Spray Standard120 - 130039Cabinet heater load conductorNOFeeds E4/A, E4/B and E4/C as applicable by model.Edit
Salt Spray Standard120 - 13004AC live accessory / chart-recorder feedYES — SHAREDInternal Illumination; Chart Recorder optionsUsed by the internal-illumination and chart-recorder branches.Edit
Salt Spray Standard120 - 1300400Chart recorder / independent PT100 option signal link via 10 Ω resistorYESChart Recorder / Independent PT100 optionEdit
Salt Spray Standard120 - 130044Internal illumination switched lamp feedYESInternal Illumination (OPTION)Edit
Salt Spray Standard120 - 1300441ACC92 option output to Y50 / V3YESACC92 optionThe drawing identifies the output as ACC92 but does not further name its function.Edit
Salt Spray Standard120 - 130045Internal illumination relay commandYESInternal Illumination (OPTION)Edit
Salt Spray Standard120 - 13005Pump motor red lead (M1 / M6 via PERC010)YES — SHAREDPump Motor 2 / second pump shares this motor-lead identifierUsed on the standard pump and the optional/model-specific second pump.Edit
Salt Spray Standard120 - 130060High water warning lampYESHigh Water Lamp (OPTION)Edit
Salt Spray Standard120 - 13007Purge solenoid Y5NOEdit
Salt Spray Standard120 - 130076Pump motor 1 commandNOEdit
Salt Spray Standard120 - 130077Pump motor 2 commandYESPump Motor 2 / second pump (Model D only)Page 6 explicitly labels Pump Motor 2 as optional; page 3 shows Model D only.Edit
Salt Spray Standard120 - 130080 V DC control railYES — SHAREDMultiple optional accessories — shared DC control railEdit
Salt Spray Standard120 - 130087Protected mains live interconnect in the mains filter / RC1 pathNOListed on page 1 as a cabinet-mains (>3 A) wire identifier.Edit
Salt Spray Standard120 - 130088Cabinet mains (>3 A) identifier listed in the wire standardNONot otherwise observed on pages 2-8 of this issue.Edit
Salt Spray Standard120 - 130096Air saturator inhibit inputNOEdit