CP Chamber Parts

Drawing evidence

Selected extraction from 15 drawing sets. Confirm model, revision, voltage and options before linking. Existing wire definitions remain separate.

Link applicable drawing

Showing up to 500 rows; narrow the search for further matches.

Drawing / revisionWireFunctionSource pagesApplicability / evidence
DRG2437 / N10PLC I8: O/T17As drawn · visually traced; provisional
DRG2437 / N100MCB26phase 1 output ; K30L1 and accessory supply2As drawn · visually traced; provisional
DRG2437 / N1000K30T1 switch edphase 1; immersion/air-saturator and cabinet-return branches3As drawn · visually traced; provisional
DRG2437 / N1001K30T2 switch edphase 2; saturator return and cabinet relay feed3As drawn · visually traced; provisional
DRG2437 / N1002K30T3 switch edphase 3; immersion return and blower-heater relay feed3As drawn · visually traced; provisional
DRG2437 / N1004MCB8 output to K1 terminal 13As drawn · visually traced; provisional
DRG2437 / N101MCB26phase 2 output ; K30L2 and PSU N terminal (live phase, not neutral)2As drawn · visually traced; provisional
DRG2437 / N102MCB26phase 3 output ; K30L3 and MCB6 input2As drawn · visually traced; provisional
DRG2437 / N11PLC I21: O/T27As drawn · visually traced; provisional
DRG2437 / N113O/T6 to E5/B blower heater3As drawn · visually traced; provisional
DRG2437 / N1133PLCC015-1: User programmable digital output 28Option-dependent · visually traced; provisional
DRG2437 / N115F2V2 terminal 4 to K6/bypass4As drawn · visually traced; provisional
DRG2437 / N116F2V2 terminal 6 to K6/bypass4As drawn · visually traced; provisional
DRG2437 / N117PLCC015-1: Sulphur dioxide supply valve8Option-dependent · visually traced; provisional
DRG2437 / N1180DO2MCB18feed18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2437 / N1181DO2NO18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2437 / N1182DO2NC18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2437 / N1183DO2common18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2437 / N123PLC I6: ACC20 full7As drawn · visually traced; provisional
DRG2437 / N1233User digital output 4 K3311Liquid immersion optional · visually traced; provisional
DRG2437 / N125PLC I14: ACC92 flow7As drawn · visually traced; provisional
DRG2437 / N1265PLCC015-2: ACC29 butterfly valve8Option-dependent · visually traced; provisional
DRG2437 / N132Pump2 red motor lead4As drawn · visually traced; provisional
DRG2437 / N133PLCC015-1: User programmable digital output 18Option-dependent · visually traced; provisional
DRG2437 / N134PLCC015-1: Spot cooler8Option-dependent · visually traced; provisional
DRG2437 / N139K4 terminal 2 to ACC47 extra front/rear mats3As drawn · visually traced; provisional
DRG2437 / N14PLC Q12: Moist air Y47As drawn · visually traced; provisional
DRG2437 / N144MCB12 output to K17 illuminationcontact feed13As drawn · visually traced; provisional
DRG2437 / N146PLC I0: ACC102 salt-solution consumption7As drawn · visually traced; provisional
DRG2437 / N147PLC I10: Salt tank low7As drawn · visually traced; provisional
DRG2437 / N148Blower BV3 position circuit link18As drawn · visually traced; provisional
DRG2437 / N1580DO4MCB22feed18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2437 / N1581DO4NO18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2437 / N1582DO4NC18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2437 / N1583DO4common18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2437 / N159Header tank Y20/Y21; also mains MCB31 output in separate reservoir branch11Liquid immersion optional · visually traced; provisional
DRG2437 / N164PLC I20: ATCU OK7As drawn · visually traced; provisional
DRG2437 / N170PLC I16: Blower valve position7As drawn · visually traced; provisional
DRG2437 / N173PLC I11: Water low7As drawn · visually traced; provisional
DRG2437 / N174PLCC035 low-level selection/lamp P711Liquid immersion optional · visually traced; provisional
DRG2437 / N177PLCC015-2: ACC29 pump changeover relay s8Option-dependent · visually traced; provisional
DRG2437 / N18PLC I9: Emergency stop7As drawn · visually traced; provisional
DRG2437 / N180User DO1MCB17feed18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2437 / N181DO1contact NO18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2437 / N182DO1contact NC18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2437 / N183DO1common18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2437 / N1891X1phase 3out to MCB26 input2As drawn · visually traced; provisional
DRG2437 / N19PLC I17: Canopy opened7As drawn · visually traced; provisional
DRG2437 / N191MCB15 output to K27 spotcooler contacts13As drawn · visually traced; provisional
DRG2437 / N197Fill pump M7 relay K14 / base-fill-open Y25 common as drawn11Liquid immersion optional · visually traced; provisional
DRG2437 / N198PLC I4: Blower heater overtemperature count7As drawn · visually traced; provisional
DRG2437 / N20PLC Q11: Auto-fill Y1 / optional Y637As drawn · visually traced; provisional
DRG2437 / N2002PLC Q5 node shared with85 feeds parallel ACC143 Y61/Y627,14Optional ; verify logic · visually traced; provisional
DRG2437 / N204Empty-base M8 motor lead111Liquid immersion optional · visually traced; provisional
DRG2437 / N205Empty-base M8 motor lead211Liquid immersion optional · visually traced; provisional
DRG2437 / N206Fillpump M7motor lead112Liquid immersion separate3phsupply · visually traced; provisional
DRG2437 / N207Fillpump M7motor lead212Liquid immersion separate3phsupply · visually traced; provisional
DRG2437 / N21PLC I12: Air saturator full7As drawn · visually traced; provisional
DRG2437 / N210PLCC015-2: Heat8Option-dependent · visually traced; provisional
DRG2437 / N211SW21 chamber-full immersion switch input11Liquid immersion optional · visually traced; provisional
DRG2437 / N212O/T13 chamber immersion-temperature input11Liquid immersion optional · visually traced; provisional
DRG2437 / N213Remote pause X17pin111Liquid immersion optional · visually traced; provisional
DRG2437 / N214Remote unpause X17pin311Liquid immersion optional · visually traced; provisional
DRG2437 / N215Remote start X16pin111Liquid immersion optional · visually traced; provisional
DRG2437 / N216Remote stop X16pin311Liquid immersion optional · visually traced; provisional
DRG2437 / N217S24two-button canopy11Liquid immersion optional · visually traced; provisional
DRG2437 / N22PLC I13: Air saturator low7As drawn · visually traced; provisional
DRG2437 / N220Chartprobe B5brown via X6pin1617Optional recorder · visually traced; provisional
DRG2437 / N221Chartprobe B5white via X6pin1517Optional recorder · visually traced; provisional
DRG2437 / N233User digital output 3 K3211Liquid immersion optional · visually traced; provisional
DRG2437 / N236S4open-contact output to Y105As drawn · visually traced; provisional
DRG2437 / N237S4close-contact output to Y115As drawn · visually traced; provisional
DRG2437 / N24+24VDC common distribution2As drawn · visually traced; provisional
DRG2437 / N241SICK relay S1 to K102contact1226As drawn · visually traced; provisional
DRG2437 / N242K102contact4 to SICKR1feedback26As drawn · visually traced; provisional
DRG2437 / N244SICK relay 14 to SPT01IM326As drawn · visually traced; provisional
DRG2437 / N248PLC I2: ACC46 purge timer7As drawn · visually traced; provisional
DRG2437 / N249PLC I1: SO2 dose feedback7As drawn · visually traced; provisional
DRG2437 / N25PLC Q10: Open canopy via S47As drawn · visually traced; provisional
DRG2437 / N250PLC Q14: ACC46 air bar Y60; safety-option paths unresolved; Low-water S17/S16 interlink (2000/2600 variant); also ACC46 air-bar identifier; Reservoirdeltaheater E6 node; distinct from water-level and SO2uses7,5,12As drawn; As drawn; Liquid immersion separate3phsupply · visually traced; provisional
DRG2437 / N252PLCC015-1: Salt spray motor run8Option-dependent · visually traced; provisional
DRG2437 / N253Reservoirdeltaheater E6 node12Liquid immersion separate3phsupply · visually traced; provisional
DRG2437 / N254Reservoirdeltaheater E6 node12Liquid immersion separate3phsupply · visually traced; provisional
DRG2437 / N255K15pole1 output to K16L112Liquid immersion separate3phsupply · visually traced; provisional
DRG2437 / N256K15pole2 output to K16L212Liquid immersion separate3phsupply · visually traced; provisional
DRG2437 / N257K15pole3 output to K16L312Liquid immersion separate3phsupply · visually traced; provisional
DRG2437 / N258K13contact to K15 coil A112Liquid immersion separate3phsupply · visually traced; provisional
DRG2437 / N259K13contact to K15 coil A212Liquid immersion separate3phsupply · visually traced; provisional
DRG2437 / N26PLC Q13: Dry air Y37As drawn · visually traced; provisional
DRG2437 / N260O/T9 to O/T1511Liquid immersion optional · visually traced; provisional
DRG2437 / N261O/T15 to O/T1611Liquid immersion optional · visually traced; provisional
DRG2437 / N262O/T16 to Y25 signal node11Liquid immersion optional · visually traced; provisional
DRG2437 / N263MCB13 output ; N1controllerpin9 and control mains12Liquid immersion separate3phsupply · visually traced; provisional
DRG2437 / N264MCB14 output ; N1controllerpin10 and control mains12Liquid immersion separate3phsupply · visually traced; provisional
DRG2437 / N265PLCC015-2: Run8Option-dependent · visually traced; provisional
DRG2437 / N27PLC Q9: Close canopy via S47As drawn · visually traced; provisional
DRG2437 / N270N1controllerpins1/17link12Liquid immersion separate3phsupply · visually traced; provisional
DRG2437 / N271N1pin16 to K16A112Liquid immersion separate3phsupply · visually traced; provisional
DRG2437 / N272N1pin3 to K16A212Liquid immersion separate3phsupply · visually traced; provisional
DRG2437 / N275MCB12 output to K15pole112Liquid immersion separate3phsupply · visually traced; provisional
DRG2437 / N28PLC I18: Canopy closed / SO2 safety branch7As drawn · visually traced; provisional
DRG2437 / N282Q2pole1 to MCB1212Liquid immersion separate3phsupply · visually traced; provisional
DRG2437 / N283Q2pole2 to MCB1312Liquid immersion separate3phsupply · visually traced; provisional
DRG2437 / N284Q2pole3 to MCB1412Liquid immersion separate3phsupply · visually traced; provisional
DRG2437 / N286PLCC015-2: Humidify8Option-dependent · visually traced; provisional
DRG2437 / N289PLCC015-2: P_Fill8Option-dependent · visually traced; provisional
DRG2437 / N31Pump1 black motor lead4As drawn · visually traced; provisional
DRG2437 / N311PLC Q6: Air curtain Y337As drawn · visually traced; provisional
DRG2437 / N32Pump2 black motor lead4As drawn · visually traced; provisional
DRG2437 / N320B1cabinet PT100white9As drawn · visually traced; provisional
DRG2437 / N321B1cabinet PT100red19As drawn · visually traced; provisional
DRG2437 / N322B1cabinet PT100red29As drawn · visually traced; provisional
DRG2437 / N323B2saturator PT100white9As drawn · visually traced; provisional
DRG2437 / N324B2saturator PT100red19As drawn · visually traced; provisional
DRG2437 / N325B2saturator PT100red29As drawn · visually traced; provisional
DRG2437 / N326Second PLCC017cardwhite lead topsychrometric wet B29As drawn · visually traced; provisional
DRG2437 / N327Secondcardorange lead towet B29As drawn · visually traced; provisional
DRG2437 / N328Secondcardred lead towet A29As drawn · visually traced; provisional
DRG2437 / N329Secondcardyellow lead todry A19As drawn · visually traced; provisional
DRG2437 / N33PLCC015-1: Blower ball valves with position switch es8Option-dependent · visually traced; provisional
DRG2437 / N330Secondcardgreen lead todry B19As drawn · visually traced; provisional
DRG2437 / N331Secondcardbrown lead todry B19As drawn · visually traced; provisional
DRG2437 / N332ACC34PT100white9As drawn · visually traced; provisional
DRG2437 / N333ACC34PT100red19As drawn · visually traced; provisional
DRG2437 / N334ACC34PT100red29As drawn · visually traced; provisional
DRG2437 / N34PLC Q7: Buzzer7As drawn · visually traced; provisional
DRG2437 / N35K1 terminal 2 to E2 air-saturator heater3As drawn · visually traced; provisional
DRG2437 / N352K19 switch edlive toverticalspray M916As drawn · visually traced; provisional
DRG2437 / N353MCB16 output to K19contact feed16As drawn · visually traced; provisional
DRG2437 / N36PLC Q4: Air saturator heater K17As drawn · visually traced; provisional
DRG2437 / N37PLC Q2: Chamber heater K2 and optional K47As drawn · visually traced; provisional
DRG2437 / N374ACC20run switch X7pin4 to K29 coil13As drawn · visually traced; provisional
DRG2437 / N375ACC20motor brown/white lead via X7pin7 to K29contact13As drawn · visually traced; provisional
DRG2437 / N377SO2K102contact10 input ; source says PLCC006 despite output card117 elsewhere26As drawn · visually traced; provisional
DRG2437 / N38PLC Q3: Immersion heater K107As drawn · visually traced; provisional
DRG2437 / N39K2 terminal 2 tofive cabinet mats; built-in130C thermostats in opposite legs3As drawn · visually traced; provisional
DRG2437 / N4MCB6 output ; PSU L and accessory feeds2As drawn · visually traced; provisional
DRG2437 / N401Multi-solution pump M14 and M16 reference discrepancy10Optional · visually traced; provisional
DRG2437 / N402PLCC015-2: Multi-solution M168Option-dependent · visually traced; provisional
DRG2437 / N403Water-fog pump M1310Optional · visually traced; provisional
DRG2437 / N404PLCC015-2: Multi-solution M178Option-dependent · visually traced; provisional
DRG2437 / N405PLCC015-2: Additional atomiser M108Option-dependent · visually traced; provisional
DRG2437 / N406Multi-solution valve Y2910Optional · visually traced; provisional
DRG2437 / N407Water-fog valve Y2810Optional · visually traced; provisional
DRG2437 / N410M10 controller terminal 4 lead10Optional pump harness · visually traced; provisional
DRG2437 / N412M10 controller terminal 6 lead10Optional pump harness · visually traced; provisional
DRG2437 / N413M16 controller terminal 4 lead10Optional pump harness · visually traced; provisional
DRG2437 / N414M16 controller terminal 6 lead10Optional pump harness · visually traced; provisional
DRG2437 / N415M11 controller terminal 4 lead10Optional pump harness · visually traced; provisional
DRG2437 / N416M17 controller terminal 4 lead10Optional pump harness · visually traced; provisional
DRG2437 / N417M11 controller terminal 6 lead10Optional pump harness · visually traced; provisional
DRG2437 / N418M17 controller terminal 6 lead10Optional pump harness · visually traced; provisional
DRG2437 / N419M12 controller terminal 4 lead10Optional pump harness · visually traced; provisional
DRG2437 / N422M12 controller terminal 6 lead10Optional pump harness · visually traced; provisional
DRG2437 / N424M13 controller terminal 4 lead10Optional pump harness · visually traced; provisional
DRG2437 / N425M13 controller terminal 6 lead10Optional pump harness · visually traced; provisional
DRG2437 / N426M14 controller terminal 4 lead10Optional pump harness · visually traced; provisional
DRG2437 / N427M14 controller terminal 6 lead10Optional pump harness · visually traced; provisional
DRG2437 / N428M15-option10 controller terminal 6 lead10Optional pump harness · visually traced; provisional
DRG2437 / N429M15-option10 controller terminal 4 lead10Optional pump harness · visually traced; provisional
DRG2437 / N430PLCC015-2: Compressor8Option-dependent · visually traced; provisional
DRG2437 / N431M10 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2437 / N432M10 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2437 / N433M11 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2437 / N434M11 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2437 / N435M12 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2437 / N436M12 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2437 / N437M13 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2437 / N438M13 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2437 / N439M14 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2437 / N44K17contact output to P10lamp13As drawn · visually traced; provisional
DRG2437 / N440M14 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2437 / N441PLCC015-1: Salt scrubber valve8Option-dependent · visually traced; provisional
DRG2437 / N442M15-option10 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2437 / N443M15-option10 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2437 / N444M16 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2437 / N445M16 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2437 / N446M17 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2437 / N447M17 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2437 / N45PLCC015-1: Interior illumination8Option-dependent · visually traced; provisional
DRG2437 / N450PLCC015-1: Salt spray purge valve8Option-dependent · visually traced; provisional
DRG2437 / N463PLCC015-1: Salt spray pressure-release valve8Option-dependent · visually traced; provisional
DRG2437 / N470PLCC015-1: Guardian Angel fatal8Option-dependent · visually traced; provisional
DRG2437 / N471PLCC015-1: Guardian Angel non-fatal8Option-dependent · visually traced; provisional
DRG2437 / N472PLCC015-1: Guardian Angel healthy8Option-dependent · visually traced; provisional
DRG2437 / N474PLCC015-2: Additional atomiser M118Option-dependent · visually traced; provisional
DRG2437 / N475Water-fog pump M1210Optional · visually traced; provisional
DRG2437 / N48PLCC015-1: Blower heater K38Option-dependent · visually traced; provisional
DRG2437 / N480PLC I7: Spraybar parked7As drawn · visually traced; provisional
DRG2437 / N5Pump1 red motor lead4As drawn · visually traced; provisional
DRG2437 / N50PLCC015-1: Wash-down valve8Option-dependent · visually traced; provisional
DRG2437 / N500PLCC015-2: Oscillating spraybar engage8Option-dependent · visually traced; provisional
DRG2437 / N502Oscillating M15 motor lead to F2V6 terminal 615As drawn · visually traced; provisional
DRG2437 / N54K10 terminal 2 to E7/A and E7/B parallel immersion heaters3As drawn · visually traced; provisional
DRG2437 / N560PLCC015-2: Dehumidify8Option-dependent · visually traced; provisional
DRG2437 / N563Multi-solution valve Y3010Optional · visually traced; provisional
DRG2437 / N564Multi-solution pump M1510Optional · visually traced; provisional
DRG2437 / N58PLCC015-2: Salt spray air valve8Option-dependent · visually traced; provisional
DRG2437 / N580DO3MCB21feed18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2437 / N581DO3NO18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2437 / N582DO3NC18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2437 / N583DO3common18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2437 / N59PLC Q15: Base fill Y97As drawn · visually traced; provisional
DRG2437 / N6Humidity RH1white signal to PLCC017-19As drawn · visually traced; provisional
DRG2437 / N60PLCC015-1: High-water warning lamp8Option-dependent · visually traced; provisional
DRG2437 / N63PLC I22: O/T87As drawn · visually traced; provisional
DRG2437 / N64PLC I23: O/T77As drawn · visually traced; provisional
DRG2437 / N65PLC I5: O/T127As drawn · visually traced; provisional
DRG2437 / N68PLCC015-2: Cool8Option-dependent · visually traced; provisional
DRG2437 / N71PLCC035 temperature/overtemperature chain via X6pin111Liquid immersion optional · visually traced; provisional
DRG2437 / N72PLCC035 high selection/lamp P911Liquid immersion optional · visually traced; provisional
DRG2437 / N73PLCC035 OK selection/lamp P811Liquid immersion optional · visually traced; provisional
DRG2437 / N74F2V1 terminal 4 to K6/bypass4As drawn · visually traced; provisional
DRG2437 / N75F2V1 terminal 6 to K6/bypass4As drawn · visually traced; provisional
DRG2437 / N76PLC Q0: Pump1 pulse7As drawn · visually traced; provisional
DRG2437 / N77PLC Q1: Pump2 pulse / optional ACC46 timer7As drawn · visually traced; provisional
DRG2437 / N80VDC control return; PSU negative earth bond shown2As drawn · visually traced; provisional
DRG2437 / N85PLC Q5: Base drain close Y77As drawn · visually traced; provisional
DRG2437 / N871X1phase 1out to MCB26 input2As drawn · visually traced; provisional
DRG2437 / N881X1phase 2out to MCB26 input2As drawn · visually traced; provisional
DRG2437 / N9Air-pressure S5black signal to PLCC017-19As drawn · visually traced; provisional
DRG2437 / N900PLC I3: Low air pressure2 S20 optional ACC467As drawn · visually traced; provisional
DRG2437 / N91PLC I19: Low air pressure17As drawn · visually traced; provisional
DRG2437 / N92Base-empty Y22/Y23 and empty-pump K1811Liquid immersion optional · visually traced; provisional
DRG2437 / N93Reservoir heater permissive K1311Liquid immersion optional · visually traced; provisional
DRG2437 / N96PLC I15: Air saturator inhibit7As drawn · visually traced; provisional
DRG2437 / N97K3 terminal 2 toblower heaters E5/A,E5/B3As drawn · visually traced; provisional
DRG2437 / N98O/T3 to E5/A blower heater3As drawn · visually traced; provisional
DRG2437 / NEProtective earth2As drawn · visually traced; provisional
DRG2437 / NL1Incoming phase 1; grey or numbered core2As drawn · visually traced; provisional
DRG2437 / NL2Incoming phase 2; black or numbered core2As drawn · visually traced; provisional
DRG2437 / NL3Incoming phase 3; brown or numbered core2As drawn · visually traced; provisional
DRG2437 / NNLegend only; no neutral in actual supply topology1As drawn · visually traced; provisional
DRG2438 / N10PLC I8: O/T17As drawn · visually traced; provisional
DRG2438 / N100MCB26 phase 1 output to K30 L12As drawn; option-dependent · source reviewed; provisional
DRG2438 / N1000K30 T1 switched phase 1 to immersion K10 contact 13As drawn; option-dependent · source reviewed; provisional
DRG2438 / N1001K30 T2 switched phase 2 to K2 and optional K4 contact feeds3As drawn; option-dependent · source reviewed; provisional
DRG2438 / N1002K30 T3 switched phase 3 to blower K3 contact feed3As drawn; option-dependent · source reviewed; provisional
DRG2438 / N1004MCB F8 output to K1 contact 13As drawn; option-dependent · source reviewed; provisional
DRG2438 / N101MCB26 phase 2 output to K30 L22As drawn; option-dependent · source reviewed; provisional
DRG2438 / N102MCB26 phase 3 output to K30 L3 and T1 primary2As drawn; option-dependent · source reviewed; provisional
DRG2438 / N11PLC I21: O/T27As drawn · visually traced; provisional
DRG2438 / N113O/T6 to E5/B blower heater3As drawn · visually traced; provisional
DRG2438 / N1133PLCC015-1: User programmable digital output 28Option-dependent · visually traced; provisional
DRG2438 / N115F2V2 terminal 4 to K6/bypass4As drawn · visually traced; provisional
DRG2438 / N116F2V2 terminal 6 to K6/bypass4As drawn · visually traced; provisional
DRG2438 / N117K102 switched contact 6 to SO2 valve Y2626As drawn; option-dependent · source reviewed; provisional
DRG2438 / N1180DO2MCB18feed18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2438 / N1181DO2NO18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2438 / N1182DO2NC18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2438 / N1183DO2common18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2438 / N123PLC I6: ACC20 full7As drawn · visually traced; provisional
DRG2438 / N1233User digital output 4 K3311Liquid immersion optional · visually traced; provisional
DRG2438 / N125PLC I14: ACC92 flow7As drawn · visually traced; provisional
DRG2438 / N1265PLCC015-2: ACC29 butterfly valve8Option-dependent · visually traced; provisional
DRG2438 / N132Pump2 red motor lead4As drawn · visually traced; provisional
DRG2438 / N133PLCC015-1: User programmable digital output 18Option-dependent · visually traced; provisional
DRG2438 / N134Spot-cooler relay command on sheet 13; allocation absent from sheet 8 output list13As drawn; option-dependent · source reviewed; provisional
DRG2438 / N139K4 contact 2 to ACC47 mats; return neutral 2 through thermostats3As drawn; option-dependent · source reviewed; provisional
DRG2438 / N14PLC Q12: Moist air Y47As drawn · visually traced; provisional
DRG2438 / N144MCB12 output to K17 illuminationcontact feed13As drawn · visually traced; provisional
DRG2438 / N146PLC I0: ACC102 salt-solution consumption7As drawn · visually traced; provisional
DRG2438 / N147PLC I10: Salt tank low7As drawn · visually traced; provisional
DRG2438 / N148Blower BV3 position circuit link18As drawn · visually traced; provisional
DRG2438 / N1580DO4MCB22feed18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2438 / N1581DO4NO18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2438 / N1582DO4NC18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2438 / N1583DO4common18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2438 / N15924 V header-valve control on one branch; MCB31 secondary AC output on another. Do not merge by number alone11As drawn; option-dependent · source reviewed; provisional
DRG2438 / N164PLC I20: ATCU OK7As drawn · visually traced; provisional
DRG2438 / N170PLC I16: Blower valve position7As drawn · visually traced; provisional
DRG2438 / N173PLC I11: Water low7As drawn · visually traced; provisional
DRG2438 / N174PLCC035 low-level selection/lamp P711Liquid immersion optional · visually traced; provisional
DRG2438 / N177PLCC015-2: ACC29 pump changeover relay s8Option-dependent · visually traced; provisional
DRG2438 / N18PLC I9: Emergency stop7As drawn · visually traced; provisional
DRG2438 / N180User DO1MCB17feed18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2438 / N181DO1contact NO18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2438 / N182DO1contact NC18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2438 / N183DO1common18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2438 / N1891X1phase 3out to MCB26 input2As drawn · visually traced; provisional
DRG2438 / N19PLC I17: Canopy opened7As drawn · visually traced; provisional
DRG2438 / N191MCB15 output to K27 spotcooler contacts13As drawn · visually traced; provisional
DRG2438 / N197Fill pump M7 relay K14 / base-fill-open Y25 common as drawn11Liquid immersion optional · visually traced; provisional
DRG2438 / N198PLC I4: Blower heater overtemperature count7As drawn · visually traced; provisional
DRG2438 / N2Neutral distribution through Q1 and X1; bypasses K30; heater returns and T1 primary return2,3,12As drawn; option-dependent · source reviewed; provisional
DRG2438 / N20PLC Q11: Auto-fill Y1 / optional Y637As drawn · visually traced; provisional
DRG2438 / N2002PLC Q5 node shared with85 feeds parallel ACC143 Y61/Y627,14Optional ; verify logic · visually traced; provisional
DRG2438 / N204Empty-base M8 motor lead111Liquid immersion optional · visually traced; provisional
DRG2438 / N205Empty-base M8 motor lead211Liquid immersion optional · visually traced; provisional
DRG2438 / N206Fillpump M7motor lead112Liquid immersion separate3phsupply · visually traced; provisional
DRG2438 / N207Fillpump M7motor lead212Liquid immersion separate3phsupply · visually traced; provisional
DRG2438 / N21PLC I12: Air saturator full7As drawn · visually traced; provisional
DRG2438 / N210PLCC015-2: Heat8Option-dependent · visually traced; provisional
DRG2438 / N211SW21 chamber-full immersion switch input11Liquid immersion optional · visually traced; provisional
DRG2438 / N212O/T13 chamber immersion-temperature input11Liquid immersion optional · visually traced; provisional
DRG2438 / N213Remote pause X17pin111Liquid immersion optional · visually traced; provisional
DRG2438 / N214Remote unpause X17pin311Liquid immersion optional · visually traced; provisional
DRG2438 / N215Remote start X16pin111Liquid immersion optional · visually traced; provisional
DRG2438 / N216Remote stop X16pin311Liquid immersion optional · visually traced; provisional
DRG2438 / N217S24two-button canopy11Liquid immersion optional · visually traced; provisional
DRG2438 / N22PLC I13: Air saturator low7As drawn · visually traced; provisional
DRG2438 / N220Chartprobe B5brown via X6pin1617Optional recorder · visually traced; provisional
DRG2438 / N221Chartprobe B5white via X6pin1517Optional recorder · visually traced; provisional
DRG2438 / N225T1 secondary return; PSU N and auxiliary AC load returns2,3,9,11,13,16As drawn; option-dependent · source reviewed; provisional
DRG2438 / N226T1 secondary feed to MCB6, MCB F8, MCB31, MCB15 and MCB162,3,11,13,16As drawn; option-dependent · source reviewed; provisional
DRG2438 / N233User digital output 3 K3211Liquid immersion optional · visually traced; provisional
DRG2438 / N236S4open-contact output to Y105As drawn · visually traced; provisional
DRG2438 / N237S4close-contact output to Y115As drawn · visually traced; provisional
DRG2438 / N24+24VDC common distribution2As drawn · visually traced; provisional
DRG2438 / N241SICK relay S1 to K102contact1226As drawn · visually traced; provisional
DRG2438 / N242K102contact4 to SICKR1feedback26As drawn · visually traced; provisional
DRG2438 / N244SICK relay 14 to SPT01IM326As drawn · visually traced; provisional
DRG2438 / N248PLC I2: ACC46 purge timer7As drawn · visually traced; provisional
DRG2438 / N249PLC I1: SO2 dose feedback7As drawn · visually traced; provisional
DRG2438 / N25PLC Q10: Open canopy via S47As drawn · visually traced; provisional
DRG2438 / N250Reservoir heater E6/A switched phase node; also low-water link on sheet 5 and ACC46 air-bar circuit on sheets 7/265,7,12,26As drawn; option-dependent · source reviewed; provisional
DRG2438 / N252PLCC015-1: Salt spray motor run8Option-dependent · visually traced; provisional
DRG2438 / N253Reservoir E6/B switched phase node; heater returns to neutral 212As drawn; option-dependent · source reviewed; provisional
DRG2438 / N254Reservoir E6/C switched phase node; heater returns to neutral 212As drawn; option-dependent · source reviewed; provisional
DRG2438 / N255K15pole1 output to K16L112Liquid immersion separate3phsupply · visually traced; provisional
DRG2438 / N256K15pole2 output to K16L212Liquid immersion separate3phsupply · visually traced; provisional
DRG2438 / N257K15pole3 output to K16L312Liquid immersion separate3phsupply · visually traced; provisional
DRG2438 / N258K13contact to K15 coil A112Liquid immersion separate3phsupply · visually traced; provisional
DRG2438 / N259K13contact to K15 coil A212Liquid immersion separate3phsupply · visually traced; provisional
DRG2438 / N26PLC Q13: Dry air Y37As drawn · visually traced; provisional
DRG2438 / N260O/T9 to O/T1511Liquid immersion optional · visually traced; provisional
DRG2438 / N261O/T15 to O/T1611Liquid immersion optional · visually traced; provisional
DRG2438 / N262O/T16 to Y25 signal node11Liquid immersion optional · visually traced; provisional
DRG2438 / N263Separate 230 V single-phase control supply live after isolator; N1 pin 9 and relay feeds12As drawn; option-dependent · source reviewed; provisional
DRG2438 / N265PLCC015-2: Run8Option-dependent · visually traced; provisional
DRG2438 / N266Separate 230 V single-phase control supply neutral; N1 pin 10 and relay returns12As drawn; option-dependent · source reviewed; provisional
DRG2438 / N27PLC Q9: Close canopy via S47As drawn · visually traced; provisional
DRG2438 / N270N1controllerpins1/17link12Liquid immersion separate3phsupply · visually traced; provisional
DRG2438 / N271N1pin16 to K16A112Liquid immersion separate3phsupply · visually traced; provisional
DRG2438 / N272N1pin3 to K16A212Liquid immersion separate3phsupply · visually traced; provisional
DRG2438 / N275MCB12 output to K15pole112Liquid immersion separate3phsupply · visually traced; provisional
DRG2438 / N276MCB13 output to K15 second pole12As drawn; option-dependent · source reviewed; provisional
DRG2438 / N277MCB14 output to K15 third pole12As drawn; option-dependent · source reviewed; provisional
DRG2438 / N28PLC I18: Canopy closed / SO2 safety branch7As drawn · visually traced; provisional
DRG2438 / N282Q2pole1 to MCB1212Liquid immersion separate3phsupply · visually traced; provisional
DRG2438 / N283Q2pole2 to MCB1312Liquid immersion separate3phsupply · visually traced; provisional
DRG2438 / N284Q2pole3 to MCB1412Liquid immersion separate3phsupply · visually traced; provisional
DRG2438 / N286PLCC015-2: Humidify8Option-dependent · visually traced; provisional
DRG2438 / N289PLCC015-2: P_Fill8Option-dependent · visually traced; provisional
DRG2438 / N31Pump1 black motor lead4As drawn · visually traced; provisional
DRG2438 / N311PLC Q6: Air curtain Y337As drawn · visually traced; provisional
DRG2438 / N32Pump2 black motor lead4As drawn · visually traced; provisional
DRG2438 / N320B1cabinet PT100white9As drawn · visually traced; provisional
DRG2438 / N321B1cabinet PT100red19As drawn · visually traced; provisional
DRG2438 / N322B1cabinet PT100red29As drawn · visually traced; provisional
DRG2438 / N323B2saturator PT100white9As drawn · visually traced; provisional
DRG2438 / N324B2saturator PT100red19As drawn · visually traced; provisional
DRG2438 / N325B2saturator PT100red29As drawn · visually traced; provisional
DRG2438 / N326Second PLCC017cardwhite lead topsychrometric wet B29As drawn · visually traced; provisional
DRG2438 / N327Secondcardorange lead towet B29As drawn · visually traced; provisional
DRG2438 / N328Secondcardred lead towet A29As drawn · visually traced; provisional
DRG2438 / N329Secondcardyellow lead todry A19As drawn · visually traced; provisional
DRG2438 / N33PLCC015-1: Blower ball valves with position switch es8Option-dependent · visually traced; provisional
DRG2438 / N330Secondcardgreen lead todry B19As drawn · visually traced; provisional
DRG2438 / N331Secondcardbrown lead todry B19As drawn · visually traced; provisional
DRG2438 / N332ACC34PT100white9As drawn · visually traced; provisional
DRG2438 / N333ACC34PT100red19As drawn · visually traced; provisional
DRG2438 / N334ACC34PT100red29As drawn · visually traced; provisional
DRG2438 / N34PLC Q7: Buzzer7As drawn · visually traced; provisional
DRG2438 / N35K1 contact 2 to E2 air-saturator heater; return 2253As drawn; option-dependent · source reviewed; provisional
DRG2438 / N352K19 switch edlive toverticalspray M916As drawn · visually traced; provisional
DRG2438 / N353MCB16 output to K19contact feed16As drawn · visually traced; provisional
DRG2438 / N36PLC Q4: Air saturator heater K17As drawn · visually traced; provisional
DRG2438 / N37PLC Q2: Chamber heater K2 and optional K47As drawn · visually traced; provisional
DRG2438 / N374ACC20run switch X7pin4 to K29 coil13As drawn · visually traced; provisional
DRG2438 / N375ACC20motor brown/white lead via X7pin7 to K29contact13As drawn · visually traced; provisional
DRG2438 / N377SO2 supply-valve command on sheet 8 to K102 contact 10 on sheet 26; sheet 26 module name PLCC006 conflicts with expansion-card identity8,26As drawn; option-dependent · source reviewed; provisional
DRG2438 / N38PLC Q3: Immersion heater K107As drawn · visually traced; provisional
DRG2438 / N39K2 contact 2 to cabinet mats; integral 130 C thermostats on neutral return3As drawn; option-dependent · source reviewed; provisional
DRG2438 / N4MCB6 output to PSU L and auxiliary feeds; incoming numbered-core 4 also denotes neutral in separate cable context2As drawn; option-dependent · source reviewed; provisional
DRG2438 / N401Multi-solution pump M14 and M16 reference discrepancy10Optional · visually traced; provisional
DRG2438 / N402PLCC015-2: Multi-solution M168Option-dependent · visually traced; provisional
DRG2438 / N403Water-fog pump M1310Optional · visually traced; provisional
DRG2438 / N404PLCC015-2: Multi-solution M178Option-dependent · visually traced; provisional
DRG2438 / N405PLCC015-2: Additional atomiser M108Option-dependent · visually traced; provisional
DRG2438 / N406Multi-solution valve Y2910Optional · visually traced; provisional
DRG2438 / N407Water-fog valve Y2810Optional · visually traced; provisional
DRG2438 / N410M10 controller terminal 4 lead10Optional pump harness · visually traced; provisional
DRG2438 / N412M10 controller terminal 6 lead10Optional pump harness · visually traced; provisional
DRG2438 / N413M16 controller terminal 4 lead10Optional pump harness · visually traced; provisional
DRG2438 / N414M16 controller terminal 6 lead10Optional pump harness · visually traced; provisional
DRG2438 / N415M11 controller terminal 4 lead10Optional pump harness · visually traced; provisional
DRG2438 / N416M17 controller terminal 4 lead10Optional pump harness · visually traced; provisional
DRG2438 / N417M11 controller terminal 6 lead10Optional pump harness · visually traced; provisional
DRG2438 / N418M17 controller terminal 6 lead10Optional pump harness · visually traced; provisional
DRG2438 / N419M12 controller terminal 4 lead10Optional pump harness · visually traced; provisional
DRG2438 / N422M12 controller terminal 6 lead10Optional pump harness · visually traced; provisional
DRG2438 / N424M13 controller terminal 4 lead10Optional pump harness · visually traced; provisional
DRG2438 / N425M13 controller terminal 6 lead10Optional pump harness · visually traced; provisional
DRG2438 / N426M14 controller terminal 4 lead10Optional pump harness · visually traced; provisional
DRG2438 / N427M14 controller terminal 6 lead10Optional pump harness · visually traced; provisional
DRG2438 / N428M15-option10 controller terminal 6 lead10Optional pump harness · visually traced; provisional
DRG2438 / N429M15-option10 controller terminal 4 lead10Optional pump harness · visually traced; provisional
DRG2438 / N430PLCC015-2: Compressor8Option-dependent · visually traced; provisional
DRG2438 / N431M10 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2438 / N432M10 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2438 / N433M11 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2438 / N434M11 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2438 / N435M12 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2438 / N436M12 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2438 / N437M13 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2438 / N438M13 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2438 / N439M14 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2438 / N44K17contact output to P10lamp13As drawn · visually traced; provisional
DRG2438 / N440M14 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2438 / N441PLCC015-1: Salt scrubber valve8Option-dependent · visually traced; provisional
DRG2438 / N442M15-option10 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2438 / N443M15-option10 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2438 / N444M16 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2438 / N445M16 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2438 / N446M17 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2438 / N447M17 changeover relay /motor lead10ACC29override · visually traced; provisional
DRG2438 / N45PLCC015-1: Interior illumination8Option-dependent · visually traced; provisional
DRG2438 / N450PLCC015-1: Salt spray purge valve8Option-dependent · visually traced; provisional
DRG2438 / N463PLCC015-1: Salt spray pressure-release valve8Option-dependent · visually traced; provisional
DRG2438 / N470PLCC015-1: Guardian Angel fatal8Option-dependent · visually traced; provisional
DRG2438 / N471PLCC015-1: Guardian Angel non-fatal8Option-dependent · visually traced; provisional
DRG2438 / N472PLCC015-1: Guardian Angel healthy8Option-dependent · visually traced; provisional
DRG2438 / N474PLCC015-2: Additional atomiser M118Option-dependent · visually traced; provisional
DRG2438 / N475Water-fog pump M1210Optional · visually traced; provisional
DRG2438 / N48PLCC015-1: Blower heater K38Option-dependent · visually traced; provisional
DRG2438 / N480PLC I7: Spraybar parked7As drawn · visually traced; provisional
DRG2438 / N5Pump1 red motor lead4As drawn · visually traced; provisional
DRG2438 / N50PLCC015-1: Wash-down valve8Option-dependent · visually traced; provisional
DRG2438 / N500PLCC015-2: Oscillating spraybar engage8Option-dependent · visually traced; provisional
DRG2438 / N502Oscillating M15 motor lead to F2V6 terminal 615As drawn · visually traced; provisional
DRG2438 / N54K10 contact 2 to immersion heaters; both printed E7/A; return neutral 23As drawn; option-dependent · source reviewed; provisional
DRG2438 / N560PLCC015-2: Dehumidify8Option-dependent · visually traced; provisional
DRG2438 / N563Multi-solution valve Y3010Optional · visually traced; provisional
DRG2438 / N564Multi-solution pump M1510Optional · visually traced; provisional
DRG2438 / N58PLCC015-2: Salt spray air valve8Option-dependent · visually traced; provisional
DRG2438 / N580DO3MCB21feed18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2438 / N581DO3NO18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2438 / N582DO3NC18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2438 / N583DO3common18Optional user relay contacts; external supply unspecified · visually traced; provisional
DRG2438 / N59PLC Q15: Base fill Y97As drawn · visually traced; provisional
DRG2438 / N6Humidity RH1white signal to PLCC017-19As drawn · visually traced; provisional
DRG2438 / N60PLCC015-1: High-water warning lamp8Option-dependent · visually traced; provisional
DRG2438 / N63PLC I22: O/T87As drawn · visually traced; provisional
DRG2438 / N64PLC I23: O/T77As drawn · visually traced; provisional
DRG2438 / N65PLC I5: O/T127As drawn · visually traced; provisional
DRG2438 / N68PLCC015-2: Cool8Option-dependent · visually traced; provisional
DRG2438 / N71PLCC035 temperature/overtemperature chain via X6pin111Liquid immersion optional · visually traced; provisional
DRG2438 / N72PLCC035 high selection/lamp P911Liquid immersion optional · visually traced; provisional
DRG2438 / N73PLCC035 OK selection/lamp P811Liquid immersion optional · visually traced; provisional
DRG2438 / N74F2V1 terminal 4 to K6/bypass4As drawn · visually traced; provisional
DRG2438 / N75F2V1 terminal 6 to K6/bypass4As drawn · visually traced; provisional
DRG2438 / N76PLC Q0: Pump1 pulse7As drawn · visually traced; provisional
DRG2438 / N77PLC Q1: Pump2 pulse / optional ACC46 timer7As drawn · visually traced; provisional
DRG2438 / N80VDC control return; PSU negative earth bond shown2As drawn · visually traced; provisional
DRG2438 / N85PLC Q5: Base drain close Y77As drawn · visually traced; provisional
DRG2438 / N871X1phase 1out to MCB26 input2As drawn · visually traced; provisional
DRG2438 / N881X1phase 2out to MCB26 input2As drawn · visually traced; provisional
DRG2438 / N9Air-pressure S5black signal to PLCC017-19As drawn · visually traced; provisional
DRG2438 / N900PLC I3: Low air pressure2 S20 optional ACC467As drawn · visually traced; provisional
DRG2438 / N91PLC I19: Low air pressure17As drawn · visually traced; provisional
DRG2438 / N92Base-empty Y22/Y23 and empty-pump K1811Liquid immersion optional · visually traced; provisional
DRG2438 / N93Reservoir heater permissive K1311Liquid immersion optional · visually traced; provisional
DRG2438 / N96PLC I15: Air saturator inhibit7As drawn · visually traced; provisional
DRG2438 / N97K3 contact 2 to blower heaters; returns through O/T3 and O/T6 to neutral 23As drawn; option-dependent · source reviewed; provisional
DRG2438 / N98O/T3 to E5/A blower heater3As drawn · visually traced; provisional
DRG2438 / NEProtective earth2As drawn · visually traced; provisional
DRG2438 / NL1Incoming phase 1; grey or numbered core2As drawn · visually traced; provisional
DRG2438 / NL2Incoming phase 2; black or numbered core2As drawn · visually traced; provisional
DRG2438 / NL3Incoming phase 3; brown or numbered core2As drawn · visually traced; provisional
DRG2438 / NNIncoming neutral; used in this 480 V supply2As drawn; option-dependent · source reviewed; provisional
DRG2511 / G1Live after MCB1 terminal 4; MCB3, MCB4 and K2 terminal 1 supply2,3All · visually traced; provisional
DRG2511 / G10Series overtemperature chain return after chamber O/T1 to PLC I04,6All · visually traced; provisional
DRG2511 / G1004MCB4 6 A output to K1 terminal 13All as drawn · visually traced; provisional
DRG2511 / G11Link between air saturator O/T2 and chamber O/T14All · visually traced; provisional
DRG2511 / G123ACC20 full switch via X7 pin 5 to PLC I84,6Optional ACC20 · visually traced; provisional
DRG2511 / G14PLC Q3 to moist-air solenoid Y45,6All as drawn · visually traced; provisional
DRG2511 / G147Salt tank low-level switch S22 via X13 pin 3 to PLC I34,6Optional low-level alarm · visually traced; provisional
DRG2511 / G15Q1 switched live output to MCB1 terminal 32All · visually traced; provisional
DRG2511 / G16Listed in mains wire legend only; no circuit function located1Unresolved · legend only
DRG2511 / G190Listed in mains wire legend only; no circuit function located1Unresolved · legend only
DRG2511 / G2Neutral after MCB1 terminal 2; PSU and heater returns2,3All · visually traced; provisional
DRG2511 / G20PLC Q6 to auto-fill solenoid Y15,6All as drawn · visually traced; provisional
DRG2511 / G200Listed in mains wire legend only; no circuit function located1Unresolved · legend only
DRG2511 / G21S7 full-level optical sensor black signal lead to PLC I44,6All as drawn · visually traced; provisional
DRG2511 / G22S8 low-level optical sensor black signal lead to PLC I54,6All as drawn · visually traced; provisional
DRG2511 / G24+24 V DC supply2,3,4,5,6All · visually traced; provisional
DRG2511 / G26PLC Q4 to dry-air solenoid Y35,6All as drawn · visually traced; provisional
DRG2511 / G31Pump controller PLCC513 terminal 4 (+) to M1 red motor lead3SP models · visually traced; provisional
DRG2511 / G35K1 terminal 2 to air saturator heater E23All as drawn · visually traced; provisional
DRG2511 / G36PLC Q1 to K1 coil A1; air saturator heater control3,6All as drawn · visually traced; provisional
DRG2511 / G37PLC Q2 to K2 coil A1; cabinet heater control3,6All as drawn · visually traced; provisional
DRG2511 / G38PLC Q5 to buzzer red lead; black lead returns to 83,6All as drawn · visually traced; provisional
DRG2511 / G39K2 terminal 2 to cabinet heater E4/A; parallel E4/B on model B3E4/B model B only; variant review needed · visually traced; provisional
DRG2511 / G4MCB3 output to PLCC303 PSU L; continuation Pg6,1A shown without receiving circuit2All · visually traced; provisional
DRG2511 / G5Pump controller PLCC513 terminal 6 (-) to M1 black motor lead3SP models · visually traced; provisional
DRG2511 / G7Optional output module PLCC006 Q4 to purge solenoid Y5 (ACC53)5,6Optional purge · visually traced; provisional
DRG2511 / G76PLC Q0 to pump controller PLCC513 terminal 103,6Models C+D explicitly noted at PLC · visually traced; provisional
DRG2511 / G80 V DC common and returns2,3,4,5,6All · visually traced; provisional
DRG2511 / G87Listed in mains wire legend only; no circuit function located1Unresolved · legend only