| Drawing / revision | Wire | Function | Source pages | Applicability / evidence |
|---|---|---|---|---|
| DRG2437 / N | 10 | PLC I8: O/T1 | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 100 | MCB26phase 1 output ; K30L1 and accessory supply | 2 | As drawn · visually traced; provisional |
| DRG2437 / N | 1000 | K30T1 switch edphase 1; immersion/air-saturator and cabinet-return branches | 3 | As drawn · visually traced; provisional |
| DRG2437 / N | 1001 | K30T2 switch edphase 2; saturator return and cabinet relay feed | 3 | As drawn · visually traced; provisional |
| DRG2437 / N | 1002 | K30T3 switch edphase 3; immersion return and blower-heater relay feed | 3 | As drawn · visually traced; provisional |
| DRG2437 / N | 1004 | MCB8 output to K1 terminal 1 | 3 | As drawn · visually traced; provisional |
| DRG2437 / N | 101 | MCB26phase 2 output ; K30L2 and PSU N terminal (live phase, not neutral) | 2 | As drawn · visually traced; provisional |
| DRG2437 / N | 102 | MCB26phase 3 output ; K30L3 and MCB6 input | 2 | As drawn · visually traced; provisional |
| DRG2437 / N | 11 | PLC I21: O/T2 | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 113 | O/T6 to E5/B blower heater | 3 | As drawn · visually traced; provisional |
| DRG2437 / N | 1133 | PLCC015-1: User programmable digital output 2 | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 115 | F2V2 terminal 4 to K6/bypass | 4 | As drawn · visually traced; provisional |
| DRG2437 / N | 116 | F2V2 terminal 6 to K6/bypass | 4 | As drawn · visually traced; provisional |
| DRG2437 / N | 117 | PLCC015-1: Sulphur dioxide supply valve | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 1180 | DO2MCB18feed | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2437 / N | 1181 | DO2NO | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2437 / N | 1182 | DO2NC | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2437 / N | 1183 | DO2common | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2437 / N | 123 | PLC I6: ACC20 full | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 1233 | User digital output 4 K33 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2437 / N | 125 | PLC I14: ACC92 flow | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 1265 | PLCC015-2: ACC29 butterfly valve | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 132 | Pump2 red motor lead | 4 | As drawn · visually traced; provisional |
| DRG2437 / N | 133 | PLCC015-1: User programmable digital output 1 | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 134 | PLCC015-1: Spot cooler | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 139 | K4 terminal 2 to ACC47 extra front/rear mats | 3 | As drawn · visually traced; provisional |
| DRG2437 / N | 14 | PLC Q12: Moist air Y4 | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 144 | MCB12 output to K17 illuminationcontact feed | 13 | As drawn · visually traced; provisional |
| DRG2437 / N | 146 | PLC I0: ACC102 salt-solution consumption | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 147 | PLC I10: Salt tank low | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 148 | Blower BV3 position circuit link | 18 | As drawn · visually traced; provisional |
| DRG2437 / N | 1580 | DO4MCB22feed | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2437 / N | 1581 | DO4NO | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2437 / N | 1582 | DO4NC | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2437 / N | 1583 | DO4common | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2437 / N | 159 | Header tank Y20/Y21; also mains MCB31 output in separate reservoir branch | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2437 / N | 164 | PLC I20: ATCU OK | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 170 | PLC I16: Blower valve position | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 173 | PLC I11: Water low | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 174 | PLCC035 low-level selection/lamp P7 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2437 / N | 177 | PLCC015-2: ACC29 pump changeover relay s | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 18 | PLC I9: Emergency stop | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 180 | User DO1MCB17feed | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2437 / N | 181 | DO1contact NO | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2437 / N | 182 | DO1contact NC | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2437 / N | 183 | DO1common | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2437 / N | 1891 | X1phase 3out to MCB26 input | 2 | As drawn · visually traced; provisional |
| DRG2437 / N | 19 | PLC I17: Canopy opened | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 191 | MCB15 output to K27 spotcooler contacts | 13 | As drawn · visually traced; provisional |
| DRG2437 / N | 197 | Fill pump M7 relay K14 / base-fill-open Y25 common as drawn | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2437 / N | 198 | PLC I4: Blower heater overtemperature count | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 20 | PLC Q11: Auto-fill Y1 / optional Y63 | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 2002 | PLC Q5 node shared with85 feeds parallel ACC143 Y61/Y62 | 7,14 | Optional ; verify logic · visually traced; provisional |
| DRG2437 / N | 204 | Empty-base M8 motor lead1 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2437 / N | 205 | Empty-base M8 motor lead2 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2437 / N | 206 | Fillpump M7motor lead1 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2437 / N | 207 | Fillpump M7motor lead2 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2437 / N | 21 | PLC I12: Air saturator full | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 210 | PLCC015-2: Heat | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 211 | SW21 chamber-full immersion switch input | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2437 / N | 212 | O/T13 chamber immersion-temperature input | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2437 / N | 213 | Remote pause X17pin1 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2437 / N | 214 | Remote unpause X17pin3 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2437 / N | 215 | Remote start X16pin1 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2437 / N | 216 | Remote stop X16pin3 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2437 / N | 217 | S24two-button canopy | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2437 / N | 22 | PLC I13: Air saturator low | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 220 | Chartprobe B5brown via X6pin16 | 17 | Optional recorder · visually traced; provisional |
| DRG2437 / N | 221 | Chartprobe B5white via X6pin15 | 17 | Optional recorder · visually traced; provisional |
| DRG2437 / N | 233 | User digital output 3 K32 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2437 / N | 236 | S4open-contact output to Y10 | 5 | As drawn · visually traced; provisional |
| DRG2437 / N | 237 | S4close-contact output to Y11 | 5 | As drawn · visually traced; provisional |
| DRG2437 / N | 24 | +24VDC common distribution | 2 | As drawn · visually traced; provisional |
| DRG2437 / N | 241 | SICK relay S1 to K102contact12 | 26 | As drawn · visually traced; provisional |
| DRG2437 / N | 242 | K102contact4 to SICKR1feedback | 26 | As drawn · visually traced; provisional |
| DRG2437 / N | 244 | SICK relay 14 to SPT01IM3 | 26 | As drawn · visually traced; provisional |
| DRG2437 / N | 248 | PLC I2: ACC46 purge timer | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 249 | PLC I1: SO2 dose feedback | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 25 | PLC Q10: Open canopy via S4 | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 250 | PLC Q14: ACC46 air bar Y60; safety-option paths unresolved; Low-water S17/S16 interlink (2000/2600 variant); also ACC46 air-bar identifier; Reservoirdeltaheater E6 node; distinct from water-level and SO2uses | 7,5,12 | As drawn; As drawn; Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2437 / N | 252 | PLCC015-1: Salt spray motor run | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 253 | Reservoirdeltaheater E6 node | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2437 / N | 254 | Reservoirdeltaheater E6 node | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2437 / N | 255 | K15pole1 output to K16L1 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2437 / N | 256 | K15pole2 output to K16L2 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2437 / N | 257 | K15pole3 output to K16L3 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2437 / N | 258 | K13contact to K15 coil A1 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2437 / N | 259 | K13contact to K15 coil A2 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2437 / N | 26 | PLC Q13: Dry air Y3 | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 260 | O/T9 to O/T15 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2437 / N | 261 | O/T15 to O/T16 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2437 / N | 262 | O/T16 to Y25 signal node | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2437 / N | 263 | MCB13 output ; N1controllerpin9 and control mains | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2437 / N | 264 | MCB14 output ; N1controllerpin10 and control mains | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2437 / N | 265 | PLCC015-2: Run | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 27 | PLC Q9: Close canopy via S4 | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 270 | N1controllerpins1/17link | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2437 / N | 271 | N1pin16 to K16A1 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2437 / N | 272 | N1pin3 to K16A2 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2437 / N | 275 | MCB12 output to K15pole1 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2437 / N | 28 | PLC I18: Canopy closed / SO2 safety branch | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 282 | Q2pole1 to MCB12 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2437 / N | 283 | Q2pole2 to MCB13 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2437 / N | 284 | Q2pole3 to MCB14 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2437 / N | 286 | PLCC015-2: Humidify | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 289 | PLCC015-2: P_Fill | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 31 | Pump1 black motor lead | 4 | As drawn · visually traced; provisional |
| DRG2437 / N | 311 | PLC Q6: Air curtain Y33 | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 32 | Pump2 black motor lead | 4 | As drawn · visually traced; provisional |
| DRG2437 / N | 320 | B1cabinet PT100white | 9 | As drawn · visually traced; provisional |
| DRG2437 / N | 321 | B1cabinet PT100red1 | 9 | As drawn · visually traced; provisional |
| DRG2437 / N | 322 | B1cabinet PT100red2 | 9 | As drawn · visually traced; provisional |
| DRG2437 / N | 323 | B2saturator PT100white | 9 | As drawn · visually traced; provisional |
| DRG2437 / N | 324 | B2saturator PT100red1 | 9 | As drawn · visually traced; provisional |
| DRG2437 / N | 325 | B2saturator PT100red2 | 9 | As drawn · visually traced; provisional |
| DRG2437 / N | 326 | Second PLCC017cardwhite lead topsychrometric wet B2 | 9 | As drawn · visually traced; provisional |
| DRG2437 / N | 327 | Secondcardorange lead towet B2 | 9 | As drawn · visually traced; provisional |
| DRG2437 / N | 328 | Secondcardred lead towet A2 | 9 | As drawn · visually traced; provisional |
| DRG2437 / N | 329 | Secondcardyellow lead todry A1 | 9 | As drawn · visually traced; provisional |
| DRG2437 / N | 33 | PLCC015-1: Blower ball valves with position switch es | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 330 | Secondcardgreen lead todry B1 | 9 | As drawn · visually traced; provisional |
| DRG2437 / N | 331 | Secondcardbrown lead todry B1 | 9 | As drawn · visually traced; provisional |
| DRG2437 / N | 332 | ACC34PT100white | 9 | As drawn · visually traced; provisional |
| DRG2437 / N | 333 | ACC34PT100red1 | 9 | As drawn · visually traced; provisional |
| DRG2437 / N | 334 | ACC34PT100red2 | 9 | As drawn · visually traced; provisional |
| DRG2437 / N | 34 | PLC Q7: Buzzer | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 35 | K1 terminal 2 to E2 air-saturator heater | 3 | As drawn · visually traced; provisional |
| DRG2437 / N | 352 | K19 switch edlive toverticalspray M9 | 16 | As drawn · visually traced; provisional |
| DRG2437 / N | 353 | MCB16 output to K19contact feed | 16 | As drawn · visually traced; provisional |
| DRG2437 / N | 36 | PLC Q4: Air saturator heater K1 | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 37 | PLC Q2: Chamber heater K2 and optional K4 | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 374 | ACC20run switch X7pin4 to K29 coil | 13 | As drawn · visually traced; provisional |
| DRG2437 / N | 375 | ACC20motor brown/white lead via X7pin7 to K29contact | 13 | As drawn · visually traced; provisional |
| DRG2437 / N | 377 | SO2K102contact10 input ; source says PLCC006 despite output card117 elsewhere | 26 | As drawn · visually traced; provisional |
| DRG2437 / N | 38 | PLC Q3: Immersion heater K10 | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 39 | K2 terminal 2 tofive cabinet mats; built-in130C thermostats in opposite legs | 3 | As drawn · visually traced; provisional |
| DRG2437 / N | 4 | MCB6 output ; PSU L and accessory feeds | 2 | As drawn · visually traced; provisional |
| DRG2437 / N | 401 | Multi-solution pump M14 and M16 reference discrepancy | 10 | Optional · visually traced; provisional |
| DRG2437 / N | 402 | PLCC015-2: Multi-solution M16 | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 403 | Water-fog pump M13 | 10 | Optional · visually traced; provisional |
| DRG2437 / N | 404 | PLCC015-2: Multi-solution M17 | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 405 | PLCC015-2: Additional atomiser M10 | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 406 | Multi-solution valve Y29 | 10 | Optional · visually traced; provisional |
| DRG2437 / N | 407 | Water-fog valve Y28 | 10 | Optional · visually traced; provisional |
| DRG2437 / N | 410 | M10 controller terminal 4 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2437 / N | 412 | M10 controller terminal 6 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2437 / N | 413 | M16 controller terminal 4 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2437 / N | 414 | M16 controller terminal 6 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2437 / N | 415 | M11 controller terminal 4 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2437 / N | 416 | M17 controller terminal 4 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2437 / N | 417 | M11 controller terminal 6 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2437 / N | 418 | M17 controller terminal 6 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2437 / N | 419 | M12 controller terminal 4 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2437 / N | 422 | M12 controller terminal 6 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2437 / N | 424 | M13 controller terminal 4 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2437 / N | 425 | M13 controller terminal 6 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2437 / N | 426 | M14 controller terminal 4 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2437 / N | 427 | M14 controller terminal 6 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2437 / N | 428 | M15-option10 controller terminal 6 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2437 / N | 429 | M15-option10 controller terminal 4 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2437 / N | 430 | PLCC015-2: Compressor | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 431 | M10 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2437 / N | 432 | M10 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2437 / N | 433 | M11 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2437 / N | 434 | M11 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2437 / N | 435 | M12 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2437 / N | 436 | M12 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2437 / N | 437 | M13 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2437 / N | 438 | M13 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2437 / N | 439 | M14 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2437 / N | 44 | K17contact output to P10lamp | 13 | As drawn · visually traced; provisional |
| DRG2437 / N | 440 | M14 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2437 / N | 441 | PLCC015-1: Salt scrubber valve | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 442 | M15-option10 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2437 / N | 443 | M15-option10 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2437 / N | 444 | M16 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2437 / N | 445 | M16 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2437 / N | 446 | M17 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2437 / N | 447 | M17 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2437 / N | 45 | PLCC015-1: Interior illumination | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 450 | PLCC015-1: Salt spray purge valve | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 463 | PLCC015-1: Salt spray pressure-release valve | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 470 | PLCC015-1: Guardian Angel fatal | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 471 | PLCC015-1: Guardian Angel non-fatal | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 472 | PLCC015-1: Guardian Angel healthy | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 474 | PLCC015-2: Additional atomiser M11 | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 475 | Water-fog pump M12 | 10 | Optional · visually traced; provisional |
| DRG2437 / N | 48 | PLCC015-1: Blower heater K3 | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 480 | PLC I7: Spraybar parked | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 5 | Pump1 red motor lead | 4 | As drawn · visually traced; provisional |
| DRG2437 / N | 50 | PLCC015-1: Wash-down valve | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 500 | PLCC015-2: Oscillating spraybar engage | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 502 | Oscillating M15 motor lead to F2V6 terminal 6 | 15 | As drawn · visually traced; provisional |
| DRG2437 / N | 54 | K10 terminal 2 to E7/A and E7/B parallel immersion heaters | 3 | As drawn · visually traced; provisional |
| DRG2437 / N | 560 | PLCC015-2: Dehumidify | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 563 | Multi-solution valve Y30 | 10 | Optional · visually traced; provisional |
| DRG2437 / N | 564 | Multi-solution pump M15 | 10 | Optional · visually traced; provisional |
| DRG2437 / N | 58 | PLCC015-2: Salt spray air valve | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 580 | DO3MCB21feed | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2437 / N | 581 | DO3NO | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2437 / N | 582 | DO3NC | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2437 / N | 583 | DO3common | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2437 / N | 59 | PLC Q15: Base fill Y9 | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 6 | Humidity RH1white signal to PLCC017-1 | 9 | As drawn · visually traced; provisional |
| DRG2437 / N | 60 | PLCC015-1: High-water warning lamp | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 63 | PLC I22: O/T8 | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 64 | PLC I23: O/T7 | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 65 | PLC I5: O/T12 | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 68 | PLCC015-2: Cool | 8 | Option-dependent · visually traced; provisional |
| DRG2437 / N | 71 | PLCC035 temperature/overtemperature chain via X6pin1 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2437 / N | 72 | PLCC035 high selection/lamp P9 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2437 / N | 73 | PLCC035 OK selection/lamp P8 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2437 / N | 74 | F2V1 terminal 4 to K6/bypass | 4 | As drawn · visually traced; provisional |
| DRG2437 / N | 75 | F2V1 terminal 6 to K6/bypass | 4 | As drawn · visually traced; provisional |
| DRG2437 / N | 76 | PLC Q0: Pump1 pulse | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 77 | PLC Q1: Pump2 pulse / optional ACC46 timer | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 8 | 0VDC control return; PSU negative earth bond shown | 2 | As drawn · visually traced; provisional |
| DRG2437 / N | 85 | PLC Q5: Base drain close Y7 | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 871 | X1phase 1out to MCB26 input | 2 | As drawn · visually traced; provisional |
| DRG2437 / N | 881 | X1phase 2out to MCB26 input | 2 | As drawn · visually traced; provisional |
| DRG2437 / N | 9 | Air-pressure S5black signal to PLCC017-1 | 9 | As drawn · visually traced; provisional |
| DRG2437 / N | 900 | PLC I3: Low air pressure2 S20 optional ACC46 | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 91 | PLC I19: Low air pressure1 | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 92 | Base-empty Y22/Y23 and empty-pump K18 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2437 / N | 93 | Reservoir heater permissive K13 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2437 / N | 96 | PLC I15: Air saturator inhibit | 7 | As drawn · visually traced; provisional |
| DRG2437 / N | 97 | K3 terminal 2 toblower heaters E5/A,E5/B | 3 | As drawn · visually traced; provisional |
| DRG2437 / N | 98 | O/T3 to E5/A blower heater | 3 | As drawn · visually traced; provisional |
| DRG2437 / N | E | Protective earth | 2 | As drawn · visually traced; provisional |
| DRG2437 / N | L1 | Incoming phase 1; grey or numbered core | 2 | As drawn · visually traced; provisional |
| DRG2437 / N | L2 | Incoming phase 2; black or numbered core | 2 | As drawn · visually traced; provisional |
| DRG2437 / N | L3 | Incoming phase 3; brown or numbered core | 2 | As drawn · visually traced; provisional |
| DRG2437 / N | N | Legend only; no neutral in actual supply topology | 1 | As drawn · visually traced; provisional |
| DRG2438 / N | 10 | PLC I8: O/T1 | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 100 | MCB26 phase 1 output to K30 L1 | 2 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 1000 | K30 T1 switched phase 1 to immersion K10 contact 1 | 3 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 1001 | K30 T2 switched phase 2 to K2 and optional K4 contact feeds | 3 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 1002 | K30 T3 switched phase 3 to blower K3 contact feed | 3 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 1004 | MCB F8 output to K1 contact 1 | 3 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 101 | MCB26 phase 2 output to K30 L2 | 2 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 102 | MCB26 phase 3 output to K30 L3 and T1 primary | 2 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 11 | PLC I21: O/T2 | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 113 | O/T6 to E5/B blower heater | 3 | As drawn · visually traced; provisional |
| DRG2438 / N | 1133 | PLCC015-1: User programmable digital output 2 | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 115 | F2V2 terminal 4 to K6/bypass | 4 | As drawn · visually traced; provisional |
| DRG2438 / N | 116 | F2V2 terminal 6 to K6/bypass | 4 | As drawn · visually traced; provisional |
| DRG2438 / N | 117 | K102 switched contact 6 to SO2 valve Y26 | 26 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 1180 | DO2MCB18feed | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2438 / N | 1181 | DO2NO | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2438 / N | 1182 | DO2NC | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2438 / N | 1183 | DO2common | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2438 / N | 123 | PLC I6: ACC20 full | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 1233 | User digital output 4 K33 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2438 / N | 125 | PLC I14: ACC92 flow | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 1265 | PLCC015-2: ACC29 butterfly valve | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 132 | Pump2 red motor lead | 4 | As drawn · visually traced; provisional |
| DRG2438 / N | 133 | PLCC015-1: User programmable digital output 1 | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 134 | Spot-cooler relay command on sheet 13; allocation absent from sheet 8 output list | 13 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 139 | K4 contact 2 to ACC47 mats; return neutral 2 through thermostats | 3 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 14 | PLC Q12: Moist air Y4 | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 144 | MCB12 output to K17 illuminationcontact feed | 13 | As drawn · visually traced; provisional |
| DRG2438 / N | 146 | PLC I0: ACC102 salt-solution consumption | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 147 | PLC I10: Salt tank low | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 148 | Blower BV3 position circuit link | 18 | As drawn · visually traced; provisional |
| DRG2438 / N | 1580 | DO4MCB22feed | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2438 / N | 1581 | DO4NO | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2438 / N | 1582 | DO4NC | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2438 / N | 1583 | DO4common | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2438 / N | 159 | 24 V header-valve control on one branch; MCB31 secondary AC output on another. Do not merge by number alone | 11 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 164 | PLC I20: ATCU OK | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 170 | PLC I16: Blower valve position | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 173 | PLC I11: Water low | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 174 | PLCC035 low-level selection/lamp P7 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2438 / N | 177 | PLCC015-2: ACC29 pump changeover relay s | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 18 | PLC I9: Emergency stop | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 180 | User DO1MCB17feed | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2438 / N | 181 | DO1contact NO | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2438 / N | 182 | DO1contact NC | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2438 / N | 183 | DO1common | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2438 / N | 1891 | X1phase 3out to MCB26 input | 2 | As drawn · visually traced; provisional |
| DRG2438 / N | 19 | PLC I17: Canopy opened | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 191 | MCB15 output to K27 spotcooler contacts | 13 | As drawn · visually traced; provisional |
| DRG2438 / N | 197 | Fill pump M7 relay K14 / base-fill-open Y25 common as drawn | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2438 / N | 198 | PLC I4: Blower heater overtemperature count | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 2 | Neutral distribution through Q1 and X1; bypasses K30; heater returns and T1 primary return | 2,3,12 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 20 | PLC Q11: Auto-fill Y1 / optional Y63 | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 2002 | PLC Q5 node shared with85 feeds parallel ACC143 Y61/Y62 | 7,14 | Optional ; verify logic · visually traced; provisional |
| DRG2438 / N | 204 | Empty-base M8 motor lead1 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2438 / N | 205 | Empty-base M8 motor lead2 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2438 / N | 206 | Fillpump M7motor lead1 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2438 / N | 207 | Fillpump M7motor lead2 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2438 / N | 21 | PLC I12: Air saturator full | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 210 | PLCC015-2: Heat | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 211 | SW21 chamber-full immersion switch input | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2438 / N | 212 | O/T13 chamber immersion-temperature input | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2438 / N | 213 | Remote pause X17pin1 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2438 / N | 214 | Remote unpause X17pin3 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2438 / N | 215 | Remote start X16pin1 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2438 / N | 216 | Remote stop X16pin3 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2438 / N | 217 | S24two-button canopy | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2438 / N | 22 | PLC I13: Air saturator low | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 220 | Chartprobe B5brown via X6pin16 | 17 | Optional recorder · visually traced; provisional |
| DRG2438 / N | 221 | Chartprobe B5white via X6pin15 | 17 | Optional recorder · visually traced; provisional |
| DRG2438 / N | 225 | T1 secondary return; PSU N and auxiliary AC load returns | 2,3,9,11,13,16 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 226 | T1 secondary feed to MCB6, MCB F8, MCB31, MCB15 and MCB16 | 2,3,11,13,16 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 233 | User digital output 3 K32 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2438 / N | 236 | S4open-contact output to Y10 | 5 | As drawn · visually traced; provisional |
| DRG2438 / N | 237 | S4close-contact output to Y11 | 5 | As drawn · visually traced; provisional |
| DRG2438 / N | 24 | +24VDC common distribution | 2 | As drawn · visually traced; provisional |
| DRG2438 / N | 241 | SICK relay S1 to K102contact12 | 26 | As drawn · visually traced; provisional |
| DRG2438 / N | 242 | K102contact4 to SICKR1feedback | 26 | As drawn · visually traced; provisional |
| DRG2438 / N | 244 | SICK relay 14 to SPT01IM3 | 26 | As drawn · visually traced; provisional |
| DRG2438 / N | 248 | PLC I2: ACC46 purge timer | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 249 | PLC I1: SO2 dose feedback | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 25 | PLC Q10: Open canopy via S4 | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 250 | Reservoir heater E6/A switched phase node; also low-water link on sheet 5 and ACC46 air-bar circuit on sheets 7/26 | 5,7,12,26 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 252 | PLCC015-1: Salt spray motor run | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 253 | Reservoir E6/B switched phase node; heater returns to neutral 2 | 12 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 254 | Reservoir E6/C switched phase node; heater returns to neutral 2 | 12 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 255 | K15pole1 output to K16L1 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2438 / N | 256 | K15pole2 output to K16L2 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2438 / N | 257 | K15pole3 output to K16L3 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2438 / N | 258 | K13contact to K15 coil A1 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2438 / N | 259 | K13contact to K15 coil A2 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2438 / N | 26 | PLC Q13: Dry air Y3 | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 260 | O/T9 to O/T15 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2438 / N | 261 | O/T15 to O/T16 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2438 / N | 262 | O/T16 to Y25 signal node | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2438 / N | 263 | Separate 230 V single-phase control supply live after isolator; N1 pin 9 and relay feeds | 12 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 265 | PLCC015-2: Run | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 266 | Separate 230 V single-phase control supply neutral; N1 pin 10 and relay returns | 12 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 27 | PLC Q9: Close canopy via S4 | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 270 | N1controllerpins1/17link | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2438 / N | 271 | N1pin16 to K16A1 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2438 / N | 272 | N1pin3 to K16A2 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2438 / N | 275 | MCB12 output to K15pole1 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2438 / N | 276 | MCB13 output to K15 second pole | 12 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 277 | MCB14 output to K15 third pole | 12 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 28 | PLC I18: Canopy closed / SO2 safety branch | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 282 | Q2pole1 to MCB12 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2438 / N | 283 | Q2pole2 to MCB13 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2438 / N | 284 | Q2pole3 to MCB14 | 12 | Liquid immersion separate3phsupply · visually traced; provisional |
| DRG2438 / N | 286 | PLCC015-2: Humidify | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 289 | PLCC015-2: P_Fill | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 31 | Pump1 black motor lead | 4 | As drawn · visually traced; provisional |
| DRG2438 / N | 311 | PLC Q6: Air curtain Y33 | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 32 | Pump2 black motor lead | 4 | As drawn · visually traced; provisional |
| DRG2438 / N | 320 | B1cabinet PT100white | 9 | As drawn · visually traced; provisional |
| DRG2438 / N | 321 | B1cabinet PT100red1 | 9 | As drawn · visually traced; provisional |
| DRG2438 / N | 322 | B1cabinet PT100red2 | 9 | As drawn · visually traced; provisional |
| DRG2438 / N | 323 | B2saturator PT100white | 9 | As drawn · visually traced; provisional |
| DRG2438 / N | 324 | B2saturator PT100red1 | 9 | As drawn · visually traced; provisional |
| DRG2438 / N | 325 | B2saturator PT100red2 | 9 | As drawn · visually traced; provisional |
| DRG2438 / N | 326 | Second PLCC017cardwhite lead topsychrometric wet B2 | 9 | As drawn · visually traced; provisional |
| DRG2438 / N | 327 | Secondcardorange lead towet B2 | 9 | As drawn · visually traced; provisional |
| DRG2438 / N | 328 | Secondcardred lead towet A2 | 9 | As drawn · visually traced; provisional |
| DRG2438 / N | 329 | Secondcardyellow lead todry A1 | 9 | As drawn · visually traced; provisional |
| DRG2438 / N | 33 | PLCC015-1: Blower ball valves with position switch es | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 330 | Secondcardgreen lead todry B1 | 9 | As drawn · visually traced; provisional |
| DRG2438 / N | 331 | Secondcardbrown lead todry B1 | 9 | As drawn · visually traced; provisional |
| DRG2438 / N | 332 | ACC34PT100white | 9 | As drawn · visually traced; provisional |
| DRG2438 / N | 333 | ACC34PT100red1 | 9 | As drawn · visually traced; provisional |
| DRG2438 / N | 334 | ACC34PT100red2 | 9 | As drawn · visually traced; provisional |
| DRG2438 / N | 34 | PLC Q7: Buzzer | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 35 | K1 contact 2 to E2 air-saturator heater; return 225 | 3 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 352 | K19 switch edlive toverticalspray M9 | 16 | As drawn · visually traced; provisional |
| DRG2438 / N | 353 | MCB16 output to K19contact feed | 16 | As drawn · visually traced; provisional |
| DRG2438 / N | 36 | PLC Q4: Air saturator heater K1 | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 37 | PLC Q2: Chamber heater K2 and optional K4 | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 374 | ACC20run switch X7pin4 to K29 coil | 13 | As drawn · visually traced; provisional |
| DRG2438 / N | 375 | ACC20motor brown/white lead via X7pin7 to K29contact | 13 | As drawn · visually traced; provisional |
| DRG2438 / N | 377 | SO2 supply-valve command on sheet 8 to K102 contact 10 on sheet 26; sheet 26 module name PLCC006 conflicts with expansion-card identity | 8,26 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 38 | PLC Q3: Immersion heater K10 | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 39 | K2 contact 2 to cabinet mats; integral 130 C thermostats on neutral return | 3 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 4 | MCB6 output to PSU L and auxiliary feeds; incoming numbered-core 4 also denotes neutral in separate cable context | 2 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 401 | Multi-solution pump M14 and M16 reference discrepancy | 10 | Optional · visually traced; provisional |
| DRG2438 / N | 402 | PLCC015-2: Multi-solution M16 | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 403 | Water-fog pump M13 | 10 | Optional · visually traced; provisional |
| DRG2438 / N | 404 | PLCC015-2: Multi-solution M17 | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 405 | PLCC015-2: Additional atomiser M10 | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 406 | Multi-solution valve Y29 | 10 | Optional · visually traced; provisional |
| DRG2438 / N | 407 | Water-fog valve Y28 | 10 | Optional · visually traced; provisional |
| DRG2438 / N | 410 | M10 controller terminal 4 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2438 / N | 412 | M10 controller terminal 6 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2438 / N | 413 | M16 controller terminal 4 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2438 / N | 414 | M16 controller terminal 6 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2438 / N | 415 | M11 controller terminal 4 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2438 / N | 416 | M17 controller terminal 4 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2438 / N | 417 | M11 controller terminal 6 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2438 / N | 418 | M17 controller terminal 6 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2438 / N | 419 | M12 controller terminal 4 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2438 / N | 422 | M12 controller terminal 6 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2438 / N | 424 | M13 controller terminal 4 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2438 / N | 425 | M13 controller terminal 6 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2438 / N | 426 | M14 controller terminal 4 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2438 / N | 427 | M14 controller terminal 6 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2438 / N | 428 | M15-option10 controller terminal 6 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2438 / N | 429 | M15-option10 controller terminal 4 lead | 10 | Optional pump harness · visually traced; provisional |
| DRG2438 / N | 430 | PLCC015-2: Compressor | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 431 | M10 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2438 / N | 432 | M10 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2438 / N | 433 | M11 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2438 / N | 434 | M11 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2438 / N | 435 | M12 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2438 / N | 436 | M12 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2438 / N | 437 | M13 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2438 / N | 438 | M13 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2438 / N | 439 | M14 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2438 / N | 44 | K17contact output to P10lamp | 13 | As drawn · visually traced; provisional |
| DRG2438 / N | 440 | M14 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2438 / N | 441 | PLCC015-1: Salt scrubber valve | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 442 | M15-option10 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2438 / N | 443 | M15-option10 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2438 / N | 444 | M16 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2438 / N | 445 | M16 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2438 / N | 446 | M17 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2438 / N | 447 | M17 changeover relay /motor lead | 10 | ACC29override · visually traced; provisional |
| DRG2438 / N | 45 | PLCC015-1: Interior illumination | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 450 | PLCC015-1: Salt spray purge valve | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 463 | PLCC015-1: Salt spray pressure-release valve | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 470 | PLCC015-1: Guardian Angel fatal | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 471 | PLCC015-1: Guardian Angel non-fatal | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 472 | PLCC015-1: Guardian Angel healthy | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 474 | PLCC015-2: Additional atomiser M11 | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 475 | Water-fog pump M12 | 10 | Optional · visually traced; provisional |
| DRG2438 / N | 48 | PLCC015-1: Blower heater K3 | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 480 | PLC I7: Spraybar parked | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 5 | Pump1 red motor lead | 4 | As drawn · visually traced; provisional |
| DRG2438 / N | 50 | PLCC015-1: Wash-down valve | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 500 | PLCC015-2: Oscillating spraybar engage | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 502 | Oscillating M15 motor lead to F2V6 terminal 6 | 15 | As drawn · visually traced; provisional |
| DRG2438 / N | 54 | K10 contact 2 to immersion heaters; both printed E7/A; return neutral 2 | 3 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 560 | PLCC015-2: Dehumidify | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 563 | Multi-solution valve Y30 | 10 | Optional · visually traced; provisional |
| DRG2438 / N | 564 | Multi-solution pump M15 | 10 | Optional · visually traced; provisional |
| DRG2438 / N | 58 | PLCC015-2: Salt spray air valve | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 580 | DO3MCB21feed | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2438 / N | 581 | DO3NO | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2438 / N | 582 | DO3NC | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2438 / N | 583 | DO3common | 18 | Optional user relay contacts; external supply unspecified · visually traced; provisional |
| DRG2438 / N | 59 | PLC Q15: Base fill Y9 | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 6 | Humidity RH1white signal to PLCC017-1 | 9 | As drawn · visually traced; provisional |
| DRG2438 / N | 60 | PLCC015-1: High-water warning lamp | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 63 | PLC I22: O/T8 | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 64 | PLC I23: O/T7 | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 65 | PLC I5: O/T12 | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 68 | PLCC015-2: Cool | 8 | Option-dependent · visually traced; provisional |
| DRG2438 / N | 71 | PLCC035 temperature/overtemperature chain via X6pin1 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2438 / N | 72 | PLCC035 high selection/lamp P9 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2438 / N | 73 | PLCC035 OK selection/lamp P8 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2438 / N | 74 | F2V1 terminal 4 to K6/bypass | 4 | As drawn · visually traced; provisional |
| DRG2438 / N | 75 | F2V1 terminal 6 to K6/bypass | 4 | As drawn · visually traced; provisional |
| DRG2438 / N | 76 | PLC Q0: Pump1 pulse | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 77 | PLC Q1: Pump2 pulse / optional ACC46 timer | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 8 | 0VDC control return; PSU negative earth bond shown | 2 | As drawn · visually traced; provisional |
| DRG2438 / N | 85 | PLC Q5: Base drain close Y7 | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 871 | X1phase 1out to MCB26 input | 2 | As drawn · visually traced; provisional |
| DRG2438 / N | 881 | X1phase 2out to MCB26 input | 2 | As drawn · visually traced; provisional |
| DRG2438 / N | 9 | Air-pressure S5black signal to PLCC017-1 | 9 | As drawn · visually traced; provisional |
| DRG2438 / N | 900 | PLC I3: Low air pressure2 S20 optional ACC46 | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 91 | PLC I19: Low air pressure1 | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 92 | Base-empty Y22/Y23 and empty-pump K18 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2438 / N | 93 | Reservoir heater permissive K13 | 11 | Liquid immersion optional · visually traced; provisional |
| DRG2438 / N | 96 | PLC I15: Air saturator inhibit | 7 | As drawn · visually traced; provisional |
| DRG2438 / N | 97 | K3 contact 2 to blower heaters; returns through O/T3 and O/T6 to neutral 2 | 3 | As drawn; option-dependent · source reviewed; provisional |
| DRG2438 / N | 98 | O/T3 to E5/A blower heater | 3 | As drawn · visually traced; provisional |
| DRG2438 / N | E | Protective earth | 2 | As drawn · visually traced; provisional |
| DRG2438 / N | L1 | Incoming phase 1; grey or numbered core | 2 | As drawn · visually traced; provisional |
| DRG2438 / N | L2 | Incoming phase 2; black or numbered core | 2 | As drawn · visually traced; provisional |
| DRG2438 / N | L3 | Incoming phase 3; brown or numbered core | 2 | As drawn · visually traced; provisional |
| DRG2438 / N | N | Incoming neutral; used in this 480 V supply | 2 | As drawn; option-dependent · source reviewed; provisional |
| DRG2511 / G | 1 | Live after MCB1 terminal 4; MCB3, MCB4 and K2 terminal 1 supply | 2,3 | All · visually traced; provisional |
| DRG2511 / G | 10 | Series overtemperature chain return after chamber O/T1 to PLC I0 | 4,6 | All · visually traced; provisional |
| DRG2511 / G | 1004 | MCB4 6 A output to K1 terminal 1 | 3 | All as drawn · visually traced; provisional |
| DRG2511 / G | 11 | Link between air saturator O/T2 and chamber O/T1 | 4 | All · visually traced; provisional |
| DRG2511 / G | 123 | ACC20 full switch via X7 pin 5 to PLC I8 | 4,6 | Optional ACC20 · visually traced; provisional |
| DRG2511 / G | 14 | PLC Q3 to moist-air solenoid Y4 | 5,6 | All as drawn · visually traced; provisional |
| DRG2511 / G | 147 | Salt tank low-level switch S22 via X13 pin 3 to PLC I3 | 4,6 | Optional low-level alarm · visually traced; provisional |
| DRG2511 / G | 15 | Q1 switched live output to MCB1 terminal 3 | 2 | All · visually traced; provisional |
| DRG2511 / G | 16 | Listed in mains wire legend only; no circuit function located | 1 | Unresolved · legend only |
| DRG2511 / G | 190 | Listed in mains wire legend only; no circuit function located | 1 | Unresolved · legend only |
| DRG2511 / G | 2 | Neutral after MCB1 terminal 2; PSU and heater returns | 2,3 | All · visually traced; provisional |
| DRG2511 / G | 20 | PLC Q6 to auto-fill solenoid Y1 | 5,6 | All as drawn · visually traced; provisional |
| DRG2511 / G | 200 | Listed in mains wire legend only; no circuit function located | 1 | Unresolved · legend only |
| DRG2511 / G | 21 | S7 full-level optical sensor black signal lead to PLC I4 | 4,6 | All as drawn · visually traced; provisional |
| DRG2511 / G | 22 | S8 low-level optical sensor black signal lead to PLC I5 | 4,6 | All as drawn · visually traced; provisional |
| DRG2511 / G | 24 | +24 V DC supply | 2,3,4,5,6 | All · visually traced; provisional |
| DRG2511 / G | 26 | PLC Q4 to dry-air solenoid Y3 | 5,6 | All as drawn · visually traced; provisional |
| DRG2511 / G | 31 | Pump controller PLCC513 terminal 4 (+) to M1 red motor lead | 3 | SP models · visually traced; provisional |
| DRG2511 / G | 35 | K1 terminal 2 to air saturator heater E2 | 3 | All as drawn · visually traced; provisional |
| DRG2511 / G | 36 | PLC Q1 to K1 coil A1; air saturator heater control | 3,6 | All as drawn · visually traced; provisional |
| DRG2511 / G | 37 | PLC Q2 to K2 coil A1; cabinet heater control | 3,6 | All as drawn · visually traced; provisional |
| DRG2511 / G | 38 | PLC Q5 to buzzer red lead; black lead returns to 8 | 3,6 | All as drawn · visually traced; provisional |
| DRG2511 / G | 39 | K2 terminal 2 to cabinet heater E4/A; parallel E4/B on model B | 3 | E4/B model B only; variant review needed · visually traced; provisional |
| DRG2511 / G | 4 | MCB3 output to PLCC303 PSU L; continuation Pg6,1A shown without receiving circuit | 2 | All · visually traced; provisional |
| DRG2511 / G | 5 | Pump controller PLCC513 terminal 6 (-) to M1 black motor lead | 3 | SP models · visually traced; provisional |
| DRG2511 / G | 7 | Optional output module PLCC006 Q4 to purge solenoid Y5 (ACC53) | 5,6 | Optional purge · visually traced; provisional |
| DRG2511 / G | 76 | PLC Q0 to pump controller PLCC513 terminal 10 | 3,6 | Models C+D explicitly noted at PLC · visually traced; provisional |
| DRG2511 / G | 8 | 0 V DC common and returns | 2,3,4,5,6 | All · visually traced; provisional |
| DRG2511 / G | 87 | Listed in mains wire legend only; no circuit function located | 1 | Unresolved · legend only |